Thermal Overload Relay

LR1-D

Model Reference

LR1-D 09~25ALR1-D 09~25A
LR1-D 40~80ALR1-D 40~80A
    Model Reference

Application

  • LR1-D series thermal relay is suitable for using in the circuits rated voltage up to 660V, ratedcurrent 80A, AC 50/60Hz, for over-current protection of AC motor.
  • The relay has the differentialmechanism and temperature compensation and can plug in LC1-D series AC contactor. Theproduct conforms to IEC60947-4-1 stardand.

Motion Characteristic: Three-phase Balance Motion Time

No Times of the setting current Motion time Start condition Ambient temperature
1 1.05 >2h Cold state 20±5oC
2 1.2 <2h Heat state(Following the No.1 test)
3 1.5 <4min
4 7.2 10A 2s<Tp≤10s ≤63A Cold state
10 4s<Tp≤10s >63A

Phase-losing Motion Characteristic

No Times of the setting current Motion time Start condition Ambient temperature
Any two phases Another phase
1 1.0 0.9 >2h Cold state 20±5oC
2 1.15 0 <2h Heat state(Following the No.1 test)

Technical Data

Type Number Setting range (A) Applied Contactor
LR1-D 09301 0.1~0.16 LC1-D-09~25
09302 0.16~0.25 LC1-D-09~25
09303 0.25~0.4 LC1-D-09~25
09304 0.4~0.63 LC1-D-09~25
09305 0.63~1 LC1-D-09~25
09306 1~1.6 LC1-D-09~25
09307 1.6~2.5 LC1-D-09~25
09308 2.5~4 LC1-D-09~25
09310 4~6 LC1-D-09~25
09312 5.5~8 LC1-D-09~25
09314 7~10 LC1-D-09~25
12316 10~13 LC1-D-09~25
16321 13~18 LC1-D-09~25
25322 18~25 LC1-D-09~25
40353 23~32 LC1-D-09~25
40355 30~40 LC1-D-40, 50, 63
63357 38~50 LC1-D-40, 50, 63
63359 48~57 LC1-D-40, 50, 63
63361 57~66 LC1-D-40, 50, 63
80363 63~80 LC1-D-40, 50, 63

Dimensioned

Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
LR1-D 09 ~ 25A F
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
LR1-D 09 ~ 25A Z
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
LR1-D 40 ~ 80A Z
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
Dimensioned Dimensioned Dimensioned Dimensioned Dimensioned
LR1-D 40 ~ 80A Z

Top

Disclaimer: The appearance of the products listed on this website, color, parameters are for reference only, issued a kind of LANGIR Electric Company shall prevail.
LANGIR Electric Company reserves the right to modify or cancel the relevant parameters of this website does not advance notice. If in doubt, please contact customer service hotline.