JR29 (T)
Model Reference
T25
T45
T370
Application
- JR29(T) series thermal overload relay is mainly suitable for A.C.electric power system with volt-age up to 660V, current up to 500A, 50/60Hz. It is generally used for the protection of overloadand phase-lacking in circuits with three-phase induce motors and is often made up electromag-netic starters with CJX8(B) series A.C. contactors. The product conforms to IEC60947-4-1 stardand.
- Noter: JR29-16(T16) is manually reset, automatic to the other.
Motion Characteristic: Three-phase Balance Motion Time
No | Times of the setting current | Motion time | Start condition | Ambient temperature | ||
1 | 1.05 | >2h | Cold state | 20±5oC | ||
2 | 1.2 | <2h | Heat state (Following the No.1 test) | |||
3 | 1.5 | <4min | ||||
4 | 7.2 | 10A | 2s<Tp≤10s | ≤63A | Cold state | |
10 | 4s<Tp≤10s | >63A |
Phase-losing Motion Characteristic
No | Times of the setting current | Motion time | Start condition | Ambient temperature | |
Any two phases | Another phase | ||||
1 | 1.0 | 0.9 | >2h | Cold state | 20±5oC |
2 | 1.15 | 0 | <2h | Heat state(Following the No.1 test) |
Technical Data
Type | Setting Range(A) | Applied Contactor |
JR29-16 (T16) |
0.11~0.16 | B9 B16 |
0.14~0.21 | ||
0.19~0.29 | ||
0.27~0.4 | ||
0.35~0.52 | ||
0.42~0.63 | ||
0.55~0.83 | ||
0.7~10. | ||
0.9~1.3 | ||
1.1~1.5 | ||
1.3~1.8 | ||
1.5~2.1 | ||
1.7~2.4 | ||
2.1~3 | ||
2.7~4 | ||
3.4~4.5 | ||
4~6 | ||
5.2~7.5 | ||
6.3~9 | ||
7.5~11 | ||
9~13 | ||
12~17.6 |
Type | Setting Range(A) | Applied Contactor |
JR29-25 (T25) |
0.1~0.16 | B25 B30 |
0.16~0.25 | ||
0.25~0.4 | ||
0.4~0.63 | ||
0.63~1 | ||
1~1.4 | ||
1.3~1.8 | ||
1.7~2.4 | ||
2.2~3.1 | ||
2.8~4 | ||
3.5~5 | ||
4.5~6.5 | ||
6~8.5 | ||
7.5~11 | ||
10~14 | ||
13~19 | ||
18~25 | ||
24~32 | ||
- | ||
- | ||
- | ||
- |
Type | Setting Range(A) | Applied Contactor |
JR29-45 (T45) |
0.28~4 | B37 B45 |
0.35~0.52 | ||
0.45~0.63 | ||
0.55~0.83 | ||
0.7~1 | ||
0.86~1.3 | ||
1.1~1.6 | ||
1.4~2.1 | ||
1.8~2.5 | ||
2.2~3.3 | ||
2.8~4 | ||
3.2~5.2 | ||
4.5~6.3 | ||
5.5~8.3 | ||
7~10 | ||
8.6~13 | ||
11~16 | ||
14~21 | ||
18~27 | ||
25~35 | ||
30~45 | ||
- | ||
- | ||
- |
Type | Setting Range(A) | Applied Contactor |
JR29-85 (T85) |
6~10 | B65 B85 |
8~14 | ||
12~20 | ||
17~29 | ||
25~40 | ||
35~55 | ||
45~70 | ||
60~100 | ||
JR29-105 (T105) |
27~42 | B105 |
36~52 | ||
45~63 | ||
57~82 | ||
70~105 | ||
80~115 | ||
JR29-170 (T170) |
90~130 | B170 |
100~160 | ||
140~200 | ||
JR29-250 (T250) |
100~160 | B250 |
160~250 | ||
250~400 | ||
JR29-370 (T370) |
100~160 | B370 |
160~250 | ||
250~400 | ||
310~500 |
Dimensioned