Mini Circuit Breaker
Miscellaneous
AEG-E60, E90
E60
E90
Application:
- E60, E90 AEG series circuit breaker is used in lighting distribution system or motor distribution system for protection overload and short-circuit in the system. The product is neoteris in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly, and its case and items are adopted by high fire-resistant and shockproof plastics. The product, with long life, is mainly used in AC 50Hz/60Hz single pole 230V or two, three, four pole 400V circuit for overload and short-circuit protection as well as for unfrequent on-and-off switching electric equipment and lighting circuit in normal case. The products comply with IEC 60898.
Technical Data
Type | E60, E90 |
Number of poles | 1P, 2P, 3P, 4P |
Rated Breaking Capacity(A) | 3KA, 4.5KA, 6KA, 10KA |
Ratec Current(A) | 6, 10, 16, 20, 25, 32, 40, 50, 63A |
Rated voltage AC Un | 240/415V |
Minimum operating voltage Ub min | 12V |
Tripping characteristics | B, C, D |
Selectivity class | 3 |
Mechanical/electrical endurance | 20000/10000 |
Tropicalisation acc. to IEC 60068-2 | 95%RH at 55oC |
Terminal capacity flexible/rigid cable | 25-35 mm2 |
Weight | 0.12kg |
Thermal operating limit In | 1.13-1.45 |
Magnetic operating In | B: 3-5 |
C: 5-10 |
Dimensions
BKN
BKN
Application:
- BKN series circuit breaker is used in lighting distribution system or motor distribution system for protection overload and short-circuit in the system. The product is neoteric in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly, and its case and items are adopted by high fire-resistant and shockproof plastics. The product, with long life, is mainly used in AC 50Hz/60Hz single pole 230V or two, three, four poles 400V circuit for overload and short-circuit protection as well as for unfrequent on-and-off switching electric equipment and lighting circuit in normal case. The products comply with IEC 60898.
Technical Data
Type | BKN | |
Number of poles | 1P, 2P, 3P, 4P | |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40A | 50, 63A |
Breaking Capacity(A) | 6000 | 4500 |
Rated Voltage(V) | 230/400V | |
Rated Frequency(Hz) | 50/60Hz | |
Endurance | ≥4000 | |
Circumstance Temp.(°C) | -5°C ~ +40°C | |
Electrical Life | ≥6000 | |
Mechanical Life | ≥20000 | |
Terminal protection | IP20 |
BKM
BKM
Application:
- BKM series circuit breaker are used in lighting distribution system or motor distribution system for protection overload and short-circuit in the system. The product is neoteric in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly, and its case and items are adopted by high fire-resistant and shockproof plastics. The product, with long life, is mainly used in AC 50Hz/60Hz single pole 230V or two, three, four poles 400V circuit for overload and short-circuit protection as well as for unfrequent on-and-off switching electric equipment and lighting circuit in normal case. The products comply with IEC 60898.
Technical Data
Type | BKM | |
Number of poles | 1P, 2P, 3P, 4P | |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40A | 50, 63A |
Breaking Capacity(A) | 6000 | 4500 |
Rated Voltage(V) | 230/400V | |
Rated Frequency(Hz) | 50/60Hz | |
Endurance | ≥4000 | |
Circumstance Temp.(°C) | -5°C ~ +40°C | |
Electrical Life | ≥6000 | |
Mechanical Life | ≥20000 | |
Terminal protection | IP20 |
S101, S101N Screw Miniature Circuit Breaker
S101, S101N
Application:
- The circuit breakers are suitable used in AC and DC 32A and below electric circuits of 50/60Hz, up to 380V and up to DC 250V respectively, for protection of electrical circuits and apparatus in office and residence buildings, and for protection of circuit terminals against overload and short circuit. The item is a durable protection that substitutes the traditional fuse element and can be used in each fuse socket with E27 thread according to DIN 40440.
Technical Data
Type | S101, S101N |
Number of poles | 1P |
Rated Current(A) | 2, 3, 4, 6, 10, 16, 20, 25, 32A |
Breaking Capacity(A) | 3000 |
Rated Voltage(V) | 250/ 380V |
Rated Frequency(Hz) | 50/60Hz |
Power Factor for Testing Circuit (A) | 0.65 ~ 0.70 |
Dimensions